TX7004 Intelligent Fire Alarm Control Panel
Installation & Operation Manual
1 Introduction
1.1 Overview
The TX7004 comprise of a range of analogue addressable, microprocessor based fire alarm control
equipment to offer flexibility in both design and operation. The System is modular concept for easy
tailoring of system design, to meet the full requirements of the project. The TX7004 Intelligent Fire
Alarm Control Panel is designed and manufactured to meet the requirement of BS EN54 Part 2&4.
The TX7004 is designed to provide early warning fire detection, to quickly identify the location of fire
and provide user definable text informing the occupants of the building of potential smoke spread.
Simultaneously, the TX7004 will alert and evacuate the occupants, and control all necessary auxiliary
command functions such as elevator control, air handling shut down, gas shut off & damper control,
as per the cause and effects requirements configured though Command Builder Set-up.
The TX7004 modular construction panel, capable of supervising four [4] monitored detection loops
expandable up to six [6] loops on standalone basis. Each loop is capable to accommodate of 254
addressable devices of any combination with T&A protocols, namely intelligent sounder strobe
TX7300 & intelligent sounder TX7320 complying with EN 54-3, rate of rise and fixed temperature heat
detector TX7110 complying with EN 54-5, photoelectric smoke detector TX7100 complying with EN
54-7, intelligent manual call point TX7140 complying with EN 54-11, intelligent reflective beam
detector (TX7130) complying with EN 54-12, input and output module TX7200, TX7210, TX7220
complying with EN54-18, and loop isolator TX7230 complying with EN 54-17. The T&A devices are fully
loop powered to support saving cost of the cable.
These systems incorporate a number of features to allow easy operation through a user-friendly
menu. The TX7004 has a LCD touch screen and Keypad menus for alternative operation with large
button access to operate the keypad control by fire brigade personnel providing total user-friendly
interface for browsing and programming. Added the commission features such as colour coded
loop mapping, dual address and device mismatch monitoring, one-man test, simplified command
builder's configuration that has proved to be highly rated by both commissioning and service
engineers.
The Control Panel has multiple built-in features. The loop card has built-in surge protection and the
communication card interface support multiple interface protocol such as USB, Ethernet, CAN Bus,
Serial, RS485, Fiber Optic in one singe card. The panel is Built-In Printer and 160 LED Zones Indicators.
The panel provides variety of inputs and outputs interfaces and auxiliary such as Output to Sounder,
F.P.E., Alarm and Fault output, Relays and Power Auxiliary.
Feature and Benefits
Compliance EN54-2 & N54-4
Using advance microprocessor technology with Large memory capacity
Enhance user interface combining LCD Touch screen and keypad access
Support real time visual algorithm
Enhance false alarm prevention
Keypad and PC programming
Support Multiple interface protocol such as USB/Ethernet/Can Bus/Serial/RS485/Fiber Optic
Support Loop Powered devices for extra saving on cable cost
Built-In Printer and 160 LED Zones Indicators
Commissioning Advantage
Auto Enrolling of Devices
Loop Mapping with colour coding status
Monitor device mismatch and dual address conflict
Command Builder to create requirements for fire event scenario
With Loop protection against power surge
One-man test with On/Off sounder
Programming Protection
System Capacity
Up to 4 loop
Support 254 Devices/One loop (1,016 ideal)
Network up to 512 Node
Programmable Capacity
Zones up to 3000
Sounders Groups 1-1000
Other Groups 1001- 2000
Built-in 160 LED Zones Indicator
Technical Specification
Compliance EN54-2 & 4
Input Voltage 230VAC +10%-15%, 50Hz
(120VAC, 60Hz, it is not applicable for EN54 & Not
tested by LPCB)
Input Current Consumption 1A
PSU Output To CIE 21.5~28.5VDC
Batteries Maximum Charge Capacity: 2 x 12V / 28AH
Maximum Charge Current: 1.2A
I maxA: 0.93A
I maxB: 2.53A
Minimum Quiescent Current: 0.45A(Imin)
Maximum Internal Resistance: 1.0OM
Rechargeable-Lead acid type battery
Recommended manufacturer
and model of battery: PS-12280 12V28AH (Tested With CIE By LPCB)
Networking and Interfaces
Panel to panel communication Can Bus [loop]
Number of Panels 512
Interface Port USB, RS485 Serial, RS232 Serial, Ethernet
System Capacity
Memory [Non-Volatile] 1000 Fire Events, 10,000 General Event
Zones 3,000 programmable
Total Group 3,000 programmable
Sounder Group 1,000 programmable
Common Group 2,000 programmable
Loop Specifications
Protocol/Addressing T&A, Value range from 1 to 254
No. of Loop 4 Loop
Protection Built-in 4kV Surge protection
Power rating 16~24Vdc /120mA
Cabling 1.0Km Max Length/2 x 1.5mm²solid core Fire resistance
Recommended Wiring (subject to local installation codes)
ISST-SFR3/ 711c-(cl-5) Intelligent Safety & Security Technology Limited
NoBurn XPS/ 682e/01 Ventcroft Limited
FT30 SAFFIRE/ 1134j Draka UK Limited
Context Plus/682a-(cl-3) Context Plus Ltd
FP200 Gold LSOH/ 077k/01 Prysmian Cables & Systems Limited
And all LPCB approved Fire cables
Recommended Cable Length ≤1000m
Panel Input/outputs
Programmable Relays 4 circuits: Normally Open/Close
Programmable Input 1 Circuit: Current Limited 24Vdc (for future use)
Programmable Auxiliary Power 19~28Vdc (Current Limited)
Fixed Outputs (FPE/Sounder) 2 Circuits: 18~28Vdc (Current Limited)
Indicator 24 LED Status/ 160 Zone Indicators
Display 7" TFT Touch Screen
Keypad 5 Brigade buttons and Programming Keypad
Material / Color Flat sheet Metal / with outer glass door, Orange stripe
Dimension Lx W x H 530 mm x 490 mm x 135 mm
Weight 16.70 Kg
Temperature -5ºC~+40ºC
Humidity 0 to 95% Relative Humidity, Non condensing |