Customization: | Available |
---|---|
Type: | Fire Alarm Host |
Function: | Networked |
Still deciding? Get samples of US$ 100/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
External (key-switch operated):
Internal:
External indicators:
Internal indicators:
Outputs:
Ancillary connections for expansion modules will allow the following:
Specifications
2 (0.8A supply) | 4 / 6 (1.5A supply) | 8/10/12/14/16/18 (4.0A supply) |
|
Power specifications | |||
Mains supply voltage | 230±10%V AC, 50/60Hz | 230±10%V AC, 50/60Hz | 230±10%V AC 50/60Hz |
Internal power supply | 27V DC | 27V DC | 27V DC |
Total output current limited to | 800mA at 240V AC | 1500mA at 240V AC | 4000mA at 240V AC |
Auxiliary power output | 27V DC | 27V DC | 27V DC |
Mains supply monitored for failure | Yes | Yes | Yes |
Battery charger monitored for failure | Yes | Yes | Yes |
Batteries monitored for disconnection and failure | Yes | Yes | Yes |
Detector circuit specification | |||
Number of circuits | 2 | 4 or 6 | 8, 10, 12, 14,16,or 18 |
Line fault monitored for open circuit | Yes | Yes | Yes |
Line fault monitored for short circuit | Yes (can be disabled) | Yes (can be disabled) | Yes (can be disabled) |
Line fault monitored for detector removal | Yes, if end of line monitor unit fitted in place of end of line resistor | ||
End of line resistor (supplied) value | 6.8K Ohm, 5% tolerance, 0.25W | 6.8K Ohm, 5% tolerance, 0.25W | 6.8K Ohm, 5% tolerance, 0.25W |
Detector continuity diodes | Silicone 1N4001 or Schottky type (required if end of line monitor unit fitted to give detector removal fault) | ||
Call point resistor value (not supplied) | 470 to 680 Ohm, 0.5W | 470 to 680 Ohm, 0.5W | 470 to 680 Ohm, 0.5W |
Maximum number of smoke detectors per zone | 20 (maximum detector current = 2mA) | 20 (maximum detector current = 2mA) | 20 (maximum detector current = 2mA) |
Maximum number of manual call points per zone | No limit | No limit | No limit |
Sounder circuit specifications: | |||
Number of circuits | 2 | 2 | 2 |
End of line resistor value | 6.8K Ohm, 5% tolerance, 0.25W | 6.8K Ohm, 5% tolerance, 0.25W | 6.8K Ohm, 5% tolerance, 0.25W |
Line fault monitored for open circuit | Yes | Yes | Yes |
Line fault monitored for short circuit | Yes | Yes | Yes |
Outputs fused at | 1A | 1A | 1.6A |
Maximum total output current all outputs | 800mA | 1500mA | 4000mA |
Maximum no of bells at 25mA each bell | 32 | 56 | 120 |
Maximum no of electronic sounders at 20mA | 40 | 70 | 150 |
Auxiliary relay contacts (do not connect mains voltages) | 1A 30V DC max voltage free |
1A 31V DC max voltage free |
1A 32V DC max voltage free |
Fuses-all fuses compliant to ice (EN60127 PT2) | |||
Mains terminal block | 200mA/T 20mm | 400mA/T 20mm | 630mA/T 20mm |
Sounder outputs | 1A/F 20mm | 1A/F 20mm | 1.6A/F 20mm |
Auxiliary output | 1A/F 20mm | 1A/F 20mm | 1A/F 20mm |
Battery fuse | 1.6A/F 20mm | 1.6A/F 20mm | 3A/F 20mm |
Door retaining magnets | do not use panel power supply as you will drastically reduce battery standby time | ||
Connection block | |||
Largest acceptable | 2.5mm2 | 2.5mm2 | 2.5mm2 |
Smallest acceptable conductor size | 0.75mm2 | 0.75mm2 | 0.75mm2 |
Dimensions | |||
Enclosure (width x height x depth) | 415 x 265 x 100mm | 415 x 265 x 100mm | 415 x 265 x 100mm |
Weight (without batteries) | 5100g | 5200g | 5500 |