JB-TB-TC5109 Intelligent Fire Alarm control panel is a new generation of alarm control panel that is designed and developed by our company through researching the fire-fighting market demand and summarizing the fire engineering experience for many years. This control panel adopts wall-mounted and modular design. And it has features of strong function, high reliability and flexible configuration. The system adopts large screen and color LCD display. The printer can print all system information, such as fire alarm, fault and so on. It is compatible with a series of TC addressable products, which are intelligent detectors, sounder strobe, LCD repeater panel, etc. It is the best option of fire protection engineering. Refer to the corresponding installation manuals for detailed technical parameters and installation instructions of detectors, modules and other accessory devices. This manual should be in charge of specially-assigned personnel carefully in order to be uses in the furture.
JB-TB-TC5109 Intelligent Fire Alarm control panel complies with Standard EN54-2 and EN54-4, which can be used in the fire alarm system with the features of easy installation, convenient operation and maintaining. The details are as follows:
1.1 Features
The CIE can have up to 48 zones, which can be distributed in one or more loops , with alarm and fault/disable indicators.
1-4 loops can be selected, with a maximum of 255 addressable points for a single loop, Max totaling 1020 addressable points including but not limited sounder strobe (TCSG5266) under EN54-3, addressable heat detector (JTW-ZOM-TC5162) under EN54-5, addressable photoelectric smoke detector (JTW-ZOM-TC5161) under EN54-7, manual call point (J-SAP-TCSB5264) under EN54-11,I/O module (TCMK5263) under EN54-18 and loop isolator (TCMK5260) under EN54-17.
High-speed processor has been used in this control panel with faster data processing speed and larger data capacity.
7-inch color LCD screen with display resolution of 800 × 480. Information is more visual.
Block terminals are all pluggable with clear marks, which is convenient for installation, commission and maintaining.
Programming can be operated on the panel or by computer.
The loop has strong anti-interference performance and the system is stable and reliable, convenient for field operating and commissioning.
Super data capability, available for 2000 pieces of information of each fire alarm, faults and etc.
Multi-operation levels have been applied on this control panel. Each level applies to variety operations which are protected by passwords, with the second level password of three digits and the third level password of six digits.
The control panel is capable of detecting faults from points (smoke detectors)as EN54-2 Clause 8.3.
1.2 Flexible Modularized Structure and Available Multifunction Configuration
The panel is formed up by various multifunctional modules which adopts plug-pull structure making configuration flexible and convenient installation easy and system commission and later capacity expansion with ease.
1.3 Certification instructions
The JB-TB-TC5109 Intelligent Fire Alarm control panel complies with the basic requirements of the standard EN54-2: 1997 +A1:2006 and EN54-4:1998. In addition to these basic requirements, the JB-TB-TC5109 meets the following standard optional requirement.
Technical Features
2.1 Operating Voltage
Voltage: AC230V
Frequency: 50HZ
Current: 1A
Recommended wiring: Fire cable not less than 1.5mm2
2.2 Battery
Maximum charge current: 2A
Maximum charging voltage: 27.6V (Note: 25ºC)
Type: Sealed lead-acid batteries 12V12AH*2
Maximum charge capacity: 12V / 12AH
Recommended Manufacturer and Battery Model: Kanglida,12V12AH. Powersonic,PS-12120.
Maximum internal resistance: 470mΩ
Fuse: 10A
2.3 Detection of Loop Parameters
Loop output: Polarization signal cable from control panel connected to 255 addressable devices
Loop input: Polarization signal cable returns control panel
Output voltage: 18V ~ 26.5V pulse
Output current: 0mA ~ 220mA
Cycle Type: A cycle
Recommended cable: Fireproof cable, connecting cable cross-sectional area≥1.0mm2 ; cable length≤
1000m.All LPCB approved fireproof cables
See Fig. 3-7 Terminal block diagram. The detailed wiring instructions for Fig. 3.3.2
Loop resistance, number of isolators: loop resistance
2.4 Output Circuit Parameters
2.4.1 Fire Alarm Output (HJ1 +, HJ-) Output voltage: 20VDC ~ 27VDC Output current: 0mA ~ 200mA
2.4.2 Fault Output (GZ11, GZ21) Contact capacity: 24VDC @ 1.0A
2.4.3 24V output (24V GND) Output voltage: 20VDC ~ 27VDC Output current:2A
Recommended cable: Twisted pair, connecting cable cross-sectional area≥1.0mm2 ; cable length≤ 1000m.All LPCB approved fireproof cables
Current
2.5.1 Imax A=1.36A (quiescent at fully load) Output to sounders and IO module=0.32A Output data power=0.52A
2.5.2 Imax B=3.52A ( alarm at fully load) Output to sounders and IO module=2A Output data power=0.8A Fire Output=0.2A
2.5.3 Imin=520mA (Quiescent without any load)
Specification of field Terminal
L, N, PE: AC 230V terminal and AC ground terminal; BS1, BP1, AS1, AP1: Loop Signal Bus Loop 1; P is positive. S is negative. The cable goes out from BS1 finally returns to AS1. The cable goes out from BP1 finally returns to AP1. A loop can connect 255 addressable devices; BS2,BP2,AS2,AP2: Loop Signal Bus Loop 2; P is positive. S is negative. The cable goes out from BS2 finally returns to AS2. The cable goes out from BP2 finally returns to AP2. A loop can connect 255 addressable devices; BS3,BP3,AS3,AP3: Loop Signal Bus Loop 3; P is positive. S is negative. The cable goes out from BS3 finally returns to AS3. The cable goes out from BP3 finally returns to AP3. A loop can connect 255 addressable devices; BS4,BP4,AS4,AP4: Loop Signal Bus Loop 4; P is positive. S is negative. The cable goes out from BS4 finally returns to AS4. The cable goes out from BP4 finally returns to AP4. A loop can connect 255 addressable devices; HJ+, HJ-: fire alarm output terminal. If any fire alarm occurs, the output is DC26V. GZ11,GZ21: Fault output terminals (When control panel is in normal condition, the relay is closed. When control panel is in fault state, the relay is open. When control panel has no power supply, the relay is opened.) CANL,CANH: control panel's networking CAN bus, polarity-sensitive; Not to be used. A1, B1: RS485 terminal, to connect CRT, polarity-sensitive; Not to be used. A2, B2: RS485 terminal, as backup; Not to be used. RGND: not to be used; DC24V, GND: The output DC24V is used for FPEs or sounder strobes.
Cabinet Installation
Control panel dimensions (length × width × height): 420mm × 140mm ×560mm. The control panel is mounted on the wall through 4 mounting holes, the dimensions of the mounting holes are shown in Figure 4-1. The right side of the control panel has 8 wiring holes, which are easy for wiring between the control panel and field devices.There are also 5 knock holes at the top, if the holes on the right side are not enough.
Main Power Connection
The connection terminals of JB-TB-TC5109 Intelligent Fire Alarm control panel need 230V/50Hz power to connect, as following Fig.4-2.
The ground cables (green/yellow) of input power cables needs to connect with PE terminals. TE and PE are short circuit.
The positive cable needs to connect to terminal L, and the negative wire needs to connect to terminal N.
The fuse of the main power: 3A
Note: No power supply before the installation is completed.
Appendix One Technical Parameters
control panel Capacity:
Maximum 4 loops and 1020 addressable points per CIE. Maximum 48 zones per CIE
Environment Temperature: 0ºC~+40ºC
Relative Humidity≤95, non-condensing
Power Supply:
Main Power: AC230V (1A), voltage range: +10%~-15% Standby Power: DC24V, battery: 12V/12AH sealed lead acid battery*2
|