/IR3 point infrared flame detector (hereinafter referred to as IR3 flame detector) is a small high-performance flame detector designed according to the market demand and customer's suggestions on the basis of referring to our previous flame detectors. IR3 flame detector uses a new type of narrow-band current-type infrared pyroelectric sensor, with a built-in 32-bit microprocessor and a patented (CN202010297486.5) signal processing algorithm, which can quickly identify the flame signal, accurately distinguish the real flame from the interference source, and greatly reduce the impact of environmental factors on the detector. Meet the explosion-proof, protection, corrosion resistance and other properties, while IR3 flame detector is smaller, lighter and more convenient to install.
2) Product diagram
3) Functional features
- Built-in 32-bit high-precision data processing chip with high speed, low power consumption and high performance;
- Adopt the patent (CN201420098276.3) narrow-band current-type infrared pyroelectric sensor;
- Small fires can be detected earlier;
- The detection distance is 40m (0.33metres*0.33metres*0.05m n-heptane fire);
- The perfect algorithm perfectly combines the ability of flame detection and false alarm;
- The detector is suitable for a variety of fuels;
- Suitable for heavy industry applications;
- Low maintenance cost, easy to update and improve.
4) Product parameters
spectral region |
IR:3.8~5.0μM |
angular field of view |
Viewing angle 90 |
detection range |
Combustible substance |
Fire source size |
detection range |
normal heptane |
0.1m2 fire plate |
40m |
petrol |
35m |
diesel |
35m |
paraffin |
35m |
alcohol |
30m |
paper |
30m |
methane |
0.5m high 0.2m wide |
30m |
Response time |
Fire source size |
Response time |
0.3metres×0.3metres-heptane flame |
≤10S |
Sensitivity grade |
Class I |
voltage range |
DC24V (voltage range 18 ~ 30V) |
operational current |
≤50mA (with a working status indicator light, which flashes green when in normal monitoring status; There is a fire alarm confirmation light, which is always red when the fire alarm is in state; There is a fault indicator light, and the yellow light is always on in the fault state; ) |
relay output |
Fire alarm relay, 1A@30VDC, normally open contact output, normally open contact disconnected in monitoring state and normally open contact closed in fire alarm state; |
Fault relay, 1A@30VDC, normally open contact output, normally open contact closed in monitoring state and normally open contact disconnected in fault alarm state; |
Signal output |
Relay type |
2-way fire alarm and fault relay output |
Working temperature |
-40ºC~70ºC |
storage temperature |
-40ºC~85ºC |
Working humidity |
0 ~ 96% RH (no condensation) can bear 100% condensation humidity in a short time. |
explosion proof certification |
ExdC T6 Gb/tD A21 IP66/IP67 T80ºC |
the protection grades |
IP 66 /IP67 |
Shell material |
Cast aluminum, the surface is painted (the coating is an insulating layer) |
Electrical interface |
1×3/4NPT, M25*1.5, G3/4 (adapters can be customized as required). |
measure |
120mm ×95mm ×85mm |
weight |
0.7KG |
accessory part |
Cast aluminum support |
design standards |
GB 15631-2008 Special Fire Detector and GB3836 Explosive Environment |
5) Size specification
6) Installation schematic
Installation Instructions


7) Wiring instructions