                                            Still deciding? Get samples of $ !
                                            
                                        Request Sample | 
| Customization: | Available | 
|---|---|
| Type: | Metal Detector | 
| Usage: | Metal, Temperature | 
Suppliers with verified business licenses
 Audited Supplier
                    Audited Supplier Audited by an independent third-party inspection agency
| MS1000-I Linear Detector Interface | 1.Interface for MS1000, MS1000-CR,MS1000-OD and MS1000-EP digital linear heat cable With local fire and fault indication Fire and fault relay output available Low-power design Metal case | 
| Technical Specifications Operating Voltage:24VDC Operating Voltage Range: 16VDC-28VDC Operating Current: Standby Current:≤20mA Fire Current:≤30mA Fault Current:≤25mA Operating environment: Temperature:-45ºC-60ºC Relative humidity:95% IP Rating :Ip66 Dimensions:90mm × 85mm × 52mm(L×W×H) | |
| MS1000-P End of Line Unit | End of Line Unit for MS1000, MS1000-CR,MS1000-OD and MS1000-EP digital linear heat cable The functions are balancing the signal status For Digital linear heat cable monitoring and alarm/fault simulating (Notice: "Fire Test" pushbutton is for testing use only) | 
| Technical Specifications Operating Voltage: No Electronics Operating environment: Temperature:-45ºC-60ºC Relative humidity:95% IP Rating :IP66 Dimensions:90mm×85mm×52mm(L×W×H) | 
|  | 
|  | 
| Model | Approvals/Max. Listed Spacing | |
| FM | UL/cUL | |
| MS1000  68ºC MS1000-CR 68ºC MS1000-OD 68ºC MS1000-EP 68ºC | 7.7m | 15.2m | 
| MS1000  88ºC MS1000-CR 88ºC MS1000-OD 88ºC MS1000-EP 88ºC | 7.7m | 15.2m | 
| MS1000  105ºC MS1000-CR 105ºC MS1000-OD 105ºC MS1000-EP 105ºC | 4.5m | 15.2m | 
| MS1000  138ºC MS1000-CR 138ºC MS1000-OD 138ºC MS1000-EP 138ºC | 4.5m | 15.2m | 
| MS1000  180ºC MS1000-CR 180ºC MS1000-OD 180ºC MS1000-EP 180ºC | N/A Special applications | N/A Special applications | 
|   |