2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System

Product Details
Customization: Available
Type: Fire Alarm Host
Function: Networked
Still deciding? Get samples of $ !
Order Sample
Shipping & Policy
Shipping Cost: Contact the supplier about freight and estimated delivery time.
Payment Methods:
visa mastercard discover JCB diners club american express T/T
PIX SPEI OXXO PSE OZOW
  Support payments in USD
Secure payments: Every payment you make on Made-in-China.com is protected by the platform.
Refund policy: Claim a refund if your order doesn't ship, is missing, or arrives with product issues.
Secured Trading Service
Diamond Member Since 2018

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
7
Year of Establishment
2012-07-20
  • 2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
  • 2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
  • 2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
  • 2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
  • 2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
  • 2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
Find Similar Products
  • Overview
  • Installation Instructions
Overview

Basic Info.

Model NO.
PZ1002
Usage
Fire, Smoke
Certification
CE
Alarm Volume (within 1m)
≥100dB
Networking Mode
Alarm
Receive Frequency
485/232
Wiring Mode
Sub-Line System
Weight [Without Battery ]
3kg
Number of Zones
2
Primary AC
90-270VDC
Standby Battery
2*12V
Detector Voltage(VDC)
24VDC
Maximum Number of Detectors Per Zone
30
Transport Package
Carton
Specification
108*143*40mm
Trademark
panel
Origin
China
HS Code
8531100000
Production Capacity
500000/Month

Packaging & Delivery

Package Size
30.00cm * 28.00cm * 25.00cm
Package Gross Weight
3.000kg

Product Description

Installation Instructions

 

THIS EQUIPMENT MUST ONLY BE INSTALLED AND MAINTAINED BY A SUITAYBLY SKILLED AND TECHNICALLY COMPETENT
PERSON. THIS EQUIPMENT IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED.
DO NOT CHANGE ANY PANEL CONNECTIONS WITH THE PANEL'S POWER APPLIED(MAINS OR BATTERY POWER).
INSTALLATION PROCEDURE
All cables must be installed in accordance with all applicable national, regional or local standards. In the UK this is BS 7671 IEE Wiring
Regulations and BS 5839-1, Fire detection and alarm systems for buildings: Code of practice for system design, installation and maintenance.
Fire resistant, screened cable should be used throughout the installation and Mains wiring should be segregated from extra low voltage field
wiring.
For PERMANENTLY CONNECTED equipment, a readily accessible disconnect device shall
be incorporated external to the equipment.
The general requirement for the Mains supply to the panel is fixed wiring, using 3 core
cable, (no less than 1mm² and no more than 2.5mm²), or a suitable three conductor
system fed from an isolating switched fused spur, fused at 3A. The Mains supply must
be exclusive to the panel.
HINT. As an alternative to a switched
fused spur, a double pole isolating
device (B) may be used in the Mains
feed from the Main Distribution
Board (A) to the panel (C), providing
it meets the appropriate wiring
TESTING THE PANEL
When testing the panel with the panel lid open, always isolate the Mains and disconnect the batteries. The panel can be
tested before connecting field wiring. If testing before installation, ensure the end-of-line resistors are fitted in the panel's
sounder and detector terminal blocks.
Position and connect two suitable 12V batteries in the panel as shown in Fig 3 and Fig 4 (page 1). When the batteries are
connected, the BATTER/POWER SUPPLY FAULT indicator will light and the warning beeper will sound. Connect the Mains wiring
and turn the Mains supply on. The MAINS ON indicator will light, the BATTERY/POWER SUPPLY FAULT indicator will go out and
the warning beeper will silence (providing the batteries are not flat).
WITH THE KEYSWITCH AT NORMAL POSITION
The MAINS ON indicator is lit. No other indicators are lit. No sounders are active. The push buttons are inoperative.
TURN THE KEYSWITCH TO ARM CONTROLS POSITION
Note: None of the panel's push buttons are operative unless the key switch is in the ARM CONTROLS position.
Press RESET. The ZONE FAULT and internal OPEN CIRCUIT FAULT indicators will light and the warning beeper will sound. The
MAINS ON indicator will remain lit. All the other indicators will NOT light. Release the push buttons and the panel will return to
normal.
TEST THE POWER SUPPLY MONITORING CIRCUIT
Switch off the Mains. The BATTERY/POWER SUPPLY FAULT indicator will light, the MAINS ON indicator will extinguish, and the
warning beeper will sound. Press SLIENCE ALARM/FAULT SOUNDERS and the warning beeper will silence but the
BATTERY/POWER SUPPLY FAULT indicator will remain lit. Reconnect the Mains and after a short time the panel will revert to
normal.
Disconnect the battery. THE BATTERY/ POWER SUPPLY FAULT indicator will light and the warning beeper will sound. Reconnect
the battery and after a short time the panel will revert to normal (i.e. only the MAINS ON indicator light on). Note: This test
should be carried out with a set of new and fully charged batteries - deteriorated cells will show a fault even when connected
and charged up.
TEST THE SOUNDER MONITORING CIRCUITS
DO NOT carry out this test with the ZONE FIRE indicator lit as sounder fuses F1 & F2 could blow. Ensure the end -of-line resistor
is connected across each of the sounder circuits on terminals 1 & 2, 3 & 4. Short the sounder terminals 1&2. The SOUNDER
FAULT indicator will light and the warning beeper will sound.
Press SILENCE ALARM/FAULT SOUNDERS and the warning beeper will silence but the SOUNDER FAULT indicator will stay on.
Remove the short and the panel will revert to normal. Open circuit the sounder terminals 3 & 4 by disconnecting one leg of the
end-of-line resistor. The SOUNDER FAULT indicator will light and the warning beeper will sound. Press SILENCE ALARM/FAULT
SOUNDERS and the warning beeper will silence but the SOUNDER FAULT indicator will stay on. Remake the circuit and the panel
will revert to normal.
TEST THE DETECTOR MONITORING CIRCUIT
Make sure an end-of-line device (EOLD) is connected across the zone circuit terminals. The EOLD would either be a Resistor or
Electronic Monitoring Unit (EMU) and associated Panel Module depending on the installation. Refer to Fig 5 (page 1) & EMU
instruction for connections.
The following four conditions can exist on the detector monitoring circuit:
1. Normal Condition: Current flows round the detector loop via the EOLD to monitor the wiring.
2. Open Circuit Fault: The wiring is broken at some point and the monitoring current can't flow through the EOLD.
When the wire connection is ok,and the control panel reports an open fault, you can adjust the potentiometer (VR1) to adjust
the voltage of zone.
3. Short Circuit Fault: A short circuit exists at some point and too much monitoring current flows.
4. Fire Condition: A partial short exists and the monitoring current increases but not enough to show a short circuit fault. Most
smoke detectors make a partial short when they are triggered but manual call points and other normally open switches need to
have 470 or 680Ω resistors connected in series in order to give a partial short. (Check-Resistor may be built into the Call Point -
see Fig 5, page 1.)
OPEN CIRCUIT FAULT TEST
Open circuit the zone circuit terminals by disconnecting one wire of the EOLD. The ZONE FAULT indicator and internal OPEN
CIRCUIT FAULT indicator will light. The warning beeper will also sound. Press SILENCE ALARM/FAULT SOUNDERS and the
warning beeper will silence but the indicators will stay on. Reconnect the EOLD and the panel will revert to normal.
SHORT CIRCUIT FAULT TEST
Short circuit the zone circuit terminals. The ZONE FAULT indicator and internal SHORT CIRCUIT FAULT indicator will light. The
warning beeper will also sound. Press SILENCE ALARM/FAULT SOUNDERS and the warning beeper will silence but the indicators
will stay on. Remove the short and the panel will revert to normal.
2/4FIRE CONDITION
Simulate a Fire condition by connecting and activating a Manual Call Point, or by fitting a 470 to 680Ω resistor across terminals
of ZONE. The sounder outputs will operate. The ZONE FIRE indicator will light and the warning beeper will sound. Press SILENCE
ALARM/FAULT SOUNDERS. The sounder outputs will return to normal but the ZONE FIRE indicator will still be lit and the
warning beeper will still sound. Press RESET and the panel will go back into alarm as the Fire condition is still present. Remove
the Fire condition from the detector loop. Press SILENCE ALARM/FAULT SOUNDERS, then RESET, and the panel reverts to
normal.

EXTERNAL INDICATORS 

• Reset / Resound / Test Zone Lamps 

• Evacuate 

• Silence Alarm Sounders 

• Silence Fault Sounders
 

INTERNAL INDICATORS 

• Open circuit zone fault 

• Short circuit zone fault 

• Zone isolate 

• Engineer test selected


OUTPUTS

Two sounder circuits (alarm relay contacts can be obtained by connecting a relay to a sounder circuit)

Ancillary connections for expansion modules will allow the following:

1.Repeater panels

2.Multiple sounder outputs

3.Connection to landlord panel
 

Input Voltage AC 100-240V, 50/60Hz
Internal Power Supply DC 30V 3A
Total Output Current ≤200mA @ 220V
Chipset 32-bit Micro processor
Zone 1-8 Zone(s)
Max Number of Smoke Detector per Zone 20-25 pcs
 
Capacity High EMI Immunity
Backup Battery DC 12V/2.2AH * 2 (not include)
Dimension 325x265x100mm
Operating Temperature 0ºC ~ +50ºC
Weight(Without battery) 2700g
Material  Iron

2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
2 Zone Conventional Fire Alarm Control Panel Fire for Fire Alarm System
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier