2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System

Shenzhen Puzhesi Technology Co., Ltd.
  • Audited Supplier
  • 9 yrs

Contact Supplier

Still deciding? Get samples of $ !
Request Sample

Product Highlights

  • Advanced SCM Technology: Uses advanced Single Chip Microcomputer for accurate and timely fire detection.
  • Rate of Rise & Fixed Temp: Class A2R detector suitable for smokeless fires, dusty, or steamy environments.
  • Field Addressable Coding: Easy commissioning with Hand-Held Encoder for electronic coding within 1-255.
  • Non-Polarized 2-Wire System: Simplifies wiring with non-polarized signal 2-wire connection.
  • Fast Thermal Response: Thermal sensitive element improves response speed to temperature variations.
  • Wide Operating Voltage: Operates on 18.5V to 26V loop voltage with low standby current.
  • Compact & Durable Design: ABS milky white enclosure, 100mm diameter, IP33 rating, and 110g weight.
  • EN 54 Compliance: Meets EN 54-5:2000 standard for heat detectors.

Product Images of 2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System

2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System pictures & photos
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System pictures & photos
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System pictures & photos
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System pictures & photos
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System pictures & photos
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System pictures & photos
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
  • 2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
  • 2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
    2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
  • 2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
    2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
  • 2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
    2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
  • 2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
    2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
  • 2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
    2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
  • 2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
    2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System

Find Similar Products

Product Description

JTW-ZOM-TC5162 Addressable Rate of Rise and Fixed Temperature Heat Detector (Detector) uses
advanced SCM technology. According to a variety of advanced fire criterion, detector can accurately and
timely detect the changes of ambient temperature and determine fire and then alarm.
With novel structure and attractive appearance, convenient and reliable installation, the detector is
suitable in places where may have smokeless fire, lots of dust or smoke and steam retained under normal
circumstances, such as indoor garages, kitchens, boiler rooms, generator rooms, drying rooms, power
generation, dehydrating workshop, etc.
II Features
1. Non-polarized signal 2-wire.
2. The detector can be addressed in field by using Hand-Held Encoder, easy and reliable for
commissioning.
3. Thermal sensitive element improves the response speed of temperature variation.
Technical Specifications
1. Class: A2R
2. Operating voltage
Signal bus voltage: loop 24V (18.5V~26V)
3. Operating current
Standby current: ≤ 0.3mA
Alarm current: ≤ 0.8mA
4. Indicator
Red. Flashes when polling, and illuminates in alarming.
5. Encoding method
Electronically coding (code range: one address within 1~255).
6. Wiring
Non-polarized signal 2-wire
7. Operating environment
Temperature: -10°C~+50°C
Relative Humidity: ≤95%, non-condensing
8. Dimension
Diameter: 100mm Height: 50mm (with base)
9. Ingress protection rating: IP33
Material and color of enclosure: ABS; milky white
10. Weight: about 110g
11. Mounting hole distance: 60mm
12. Standard: EN 54-5:2000
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
. Operation principle
The detector uses thermistor as its sensor and transmits the signal to a single chip which, after voltage
transfer, processes the signal using intelligent arithmetic and sends any fire alarm to the FACP. The LED
indicators will then be lit by the control panel.
Mounting and Wiring
1. Mounting
Installation of the detector is shown in Fig. 2
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
2 Base of the detector is shown in Fig. 3. Fix the base with two tapping screws, and then connect loop to
terminals (polarity-insensitive). After the base is fixed firmly, rotate the bottom of detector and base
clockwise, and then the detector will be fitted to the base.
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
3 Recommended Wiring
1.0mm2 or above fire cable,subject to local codes.
4 Warning
Before testing, please ensure that the detector has been installed correctly and powered up.
 
3 Recommended Wiring
1.0mm2 or above fire cable,subject to local codes.
4 Warning
Before testing, please ensure that the detector has been installed correctly and powered up.
1).Registration: After confirming the installation and wiring is correct, register devices to the fire alarm
control panel, and check whether the numbers of installed detectors and registered detectors are
consistent.
2).Fire simulation test: After registration, choose one detector arbitrarily, and fit it to meet fire conditions
to check whether the detector generates fire normally.
3).After testing, reset the detector. Notify the proper authorities that the system returns to normal state.
4).Clean the failure detector in the test according to Maintenance, and test it again. If it is still fail to pass,
please return it to repair.
3. Do not connect to the power supply before all detectors been installed.
Usage and Operation
1 Electronically coding for the detector makes it easy and convenient. TCBM5023 hand-held encoder made
by TC is used for field coding. When coding, connect the encoder with detector loop terminal (non-polarity)
and write or read the address code.
2 Coding step: press "2" in the main menu of the encoder to enter into "(2) mode setup" and choose "(1)
TC5000" in the sub menu. Press "(5), (6), or (7)" to choose ascending number coding, normal coding or
descending number coding. Easy application (default is TC5000, normal coding) and chosen complete, press
"erase/roll page" to enter into coding interface and press exit to return to main page. Press "1" for "(1) write
address" and connect the encoder with the detector loop terminal L1 and L2. At standby status, input
detector address (1 to 255) and press "write address". "OK" means write-in success and "fail" means not.
VIII Fault and maintenance
1. Wrong address
Check whether Hand-Held Encoder works normally, and whether battery discharge. Check whether
connection is correct, or there is a fault in circuit.
2. Cannot register
Check whether loop connection is correct, and loop voltage is 18-24V in normal. Plug firmly or there is
a fault in circuit.
3. Report fault
Read code with Hand-Held Encider, if code is correct in a state of polarity intermodulation, the detector
works normally. And then check connection or there is a fault in circuit.
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System
2 Wire En54 Addressable Fire Alarm Heat Detector for Fire Alarm System

About the Supplier

This supplier has been audited by TÜV Rheinland. Verify the report on the official TÜV Rheinland website with ID "MIC-ASR2221392". Items marked "verified" are certified.

Watch Video
Watch Video
Shenzhen Puzhesi Technology Co., Ltd.
Shenzhen Puzhesi Technology Co., Ltd.
Shenzhen Puzhesi Technology Co., Ltd.
Shenzhen Puzhesi Technology Co., Ltd.
Shenzhen Puzhesi Technology Co., Ltd.
Shenzhen Puzhesi Technology Co., Ltd.
Shenzhen Puzhesi Technology Co., Ltd.
Shenzhen Puzhesi Technology Co., Ltd.

About Our Factory & Business Background

verified Business Type
Trading Company
Address
3005-3005a, Bao De Industrial Center, Lixin Nan Road, Fuyong Town, Baoan District, Shenzhen, Guangdong, China
verified Plant Area
248 square meters
verified Number of Employees
7
verified Registered Capital
6,000,000 RMB
verified Terms of Payment
LC, T/T, D/P, PayPal, Western Union, Small-amount payment
verified International Commercial Terms(Incoterms)
FOB, CIF
verified Average Lead Time
Peak Season Lead Time: one month
Off Season Lead Time: within 15 workdays
verified Nearest Port
Shenzhen Port

Our Production Capability & Technical Expertise

verified Main Products
Fire Alarm Control Panel, Smoke Detector, Heat Detector, Conventional Beam Detector, Extinguishant Control Panel
verified R&D Engineers
1 people

Our Industry Experience & Global Business Record

verified Year of Establishment
2012-07-20
Export Year
2015-07-02
verified Main Markets
Europe, Southeast Asia/ Mideast, Domestic
verified Number of Foreign Trading Staff
4
verified Overseas Agent/Branch
No

FAQ

What is the operating voltage range?
The operating voltage is 24V (18.5V~26V) on the signal bus.
Can the detector be addressed in the field?
Yes, it can be addressed in the field using a Hand-Held Encoder for easy commissioning.
What is the address range for this detector?
The address range is from 1 to 255.
Is the wiring polarized?
No, it uses a non-polarized signal 2-wire system.
What is the ingress protection rating?
The detector has an IP33 rating.
What standards does this detector meet?
It meets the EN 54-5:2000 standard.
How is the detector mounted?
It is ceiling mounted using two tapping screws to fix the base, then rotated clockwise to fit.