• Conventional Fire Alarm Control Panel Fire Alarm System
  • Conventional Fire Alarm Control Panel Fire Alarm System
  • Conventional Fire Alarm Control Panel Fire Alarm System

Conventional Fire Alarm Control Panel Fire Alarm System

Type: Fire Alarm Host
Function: Non-Networked
Usage: Auto, Fire, Smoke
Certification: CE, RoHS
Alarm Volume (within 1m): ≥90dB
Networking Mode: GSM Dial-up
Samples:
US$ 180/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2018

Suppliers with verified business licenses

Rating: 5.0/5
Trading Company

Basic Info.

Model NO.
HP1004
Receive Frequency
Eia-485
Wiring Mode
Sub-Line System
Primary AC
90-270VAC 50/60 Hz
Transport Package
Carton
Trademark
convoy
Origin
China
Production Capacity
50000

Product Description

Conventional Fire Alarm Control Panel Fire Alarm System



General

Conventional Fire Alarm Control Panel with four Zones

Key Specifications/Special Features

 
4/8/16 Style B (Class B) Initiating Device Circuits (IDCs).
All zones accept two-wire smoke detectors and any normally-open contact devices.
One built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).
Alarm, Trouble and Supervisory, Form-C relays standard.
24-volt operation.
Resettable four-wire smoke detector power @ 500 mA.
Non-resettable power @ 500 mA.
One-man walk-test programmable for silent or audible test.
Disable/Enable control per IDC.
Reverse polarity protection.

Specifications
 

1. 16-zone fire alarm control panel (FACP). 
2.Designed with standby batteries and space provision for two sealed lead-acid
batteries.

 

1.AC Power
     220 VAC, 50 Hz, 2.3 amps
    Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation
2.Battery (lead acid only)
     Maximum Charging Circuit: Normal Flat Charge-27.6V @ 0.8 amp
     Maximum Charger Capacity: 18 Amp Hour batter
3.Sound Output Device Circuits
      General Alarm Zones 1 through 16
      Operation: All zones Class B
      Normal Operating Voltage: Nominal 24 VDC (ripple = 100 mV maximum)
      Alarm Current: 15 mA threshold
      Short Circuit Current: 42 mA maximum
       Maximum Loop Resistance: 100 ohms
       End-of-Line Resistor: 4.7K, ½ watt
       Detector Loop Current is sufficient to ensure operation of two alarmed
detectors per zone
       Standby Current: 7.26 mA
4.Three Relays Output
Relay contact rating: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC
(resistive)
5.Nonresettable 24 VDC Power
     Maximum ripple voltage: 10 mVRMS Operating Voltage nominal 24 volts
     Total DC current available from this output is up to 500 mA
     Recommended maximum Standby current is 150 mA


Conventional Fire Alarm Control Panel Fire Alarm System

 

Send your message to this supplier